100 KVAR Capacitor Bank
500 KVAR APFC Panel
APFC Panel
INTRODUCTION
All PP Capacitors have been developed to overcome the limitations of MPP Capacitors.
1. In such current due to frequent Switching.
2. Current handling Capacity, because of presence of Harmonics in the Electrical Systems.
Development in modern technology have led to a significant increase in the number of thyristor & converter fed loads & D.C. Drives. unfortunately the said equipment's have undesirable Effects on the incoming AC supply, drawing appreciable inductive reactive power & a non-sine-wave current, The Standard range MPP Capacitors are designed for systems where harmonics are not present.
The rising capacitor is accommodated by constructional improvement of Jaivic all PP Capacitors.
ECOVAR High Voltage Power Capacitors are manufactures at our Sinnar Plant in India, which is an ISO-9000 accredited facility & houses a computer aided design, manufacturing, processing and testing infrastructure that ensures all products manufactured strictly comply with domestic and international standards and perform to the highest levels of safety reliability and life expectancy
Salient Features of JAIVIC ALL PP Capacitors
1. It is two layer film design. Conductive plate thickness is high compared to PP Capacitors making the electrical stress very low.
2. Normal stress on dielectric PP film is very low.
3. ALL PP Film Capacitors are impregnated with non-toxic low viscous stabilized impregnant under high vacuum. This result in inpregnant fluid replacing air-pockets, due to this capacitors develop very good partial discharge characteristics. This attributes to voidfree impregnation of capacitors eventually developing very good partial discharge characteristics.
4. ALL PC Capacitors have the capability to bear harmonics and withstand high inrush current owing to sturdy construction. Impregnated capacitors oil results in excellent heat dissipation.
5. ALL PC Capacitors have very low losses because of the absence of paper & consequently they have very low
temperature rise.
6. Power factor of the system remains unaffected for an appreciable period of time. Highly suitable for Automatic Power Factor Correction. An excellent selection for Automatic Power Factor correction.
7. Initial cost is higher compared to MPP Capacitors but its long life & consistent unchanging performance makes it cheaper.
STANDARD RATINGS OF APP CAPACITORS & DETAILS OF ACCESSORIES
UNIT RATING IN kVAr |
VOLTAGE | RATED CURRENT AMPS | CAPACITANCE BETWEEN PHASES MFD | APPROX DIMENSIONS WITH COVER | CABLE SIZE Sq. Mm |
FUSE RATING Amps. |
SWITCHGEAR RATING Amps. |
|||
Length | Width | Height | Cu | Al | ||||||
5 | 440 | 6.6 | 41.12 | 235 | 110 | 295 | 1.5 | 2.5 | 10 | 16 |
415 | 6.9 | 46.23 | ||||||||
7.5 | 440 | 9.9 | 61.65 | 300 | 110 | 395 | 2.5 | 4 | 16 | 32 |
415 | 10.4 | 69.30 | ||||||||
10 | 440 | 13.2 | 82.20 | 300 | 110 | 395 | 4 | 6 | 20 | 32 |
415 | 13.9 | 92.46 | ||||||||
15 | 440 | 19.8 | 123.37 | 300 | 180 | 370 | 10 | 16 | 32 | 63 |
415 | 20.8 | 138.68 | ||||||||
20 | 440 | 26.4 | 164.40 | 300 | 180 | 395 | 10 | 16 | 50 | 63 |
415 | 27.8 | 184.91 | ||||||||
25 | 440 | 33 | 205.50 | 300 | 180 | 445 | 16 | 25 | 50 | 63 |
415 | 34.8 | 231.41 |